| Model | OLS2000EXL |
| Capacity(VA/W) | 2000VA / 1600W |
| Typology | Online (Double Conversion) |
| Input |
| Voltage Range | 120~139Vac for 0~25% Load
140~159Vac for 0~50% Load
160~179Vac for 0~75% Load
180~280Vac for 0~100% Load |
| Frequency Range | 40~70Hz |
| Output |
| Voltage Range | Pure Sinewave at 200, 208, 220, 230, 240Vac (Configurable) ±1% |
| Frequency Range | 50 / 60Hz (Auto-Sensing or Configurable) ±0.5Hz |
| Transfer Time (Typical) | 0ms |
| Overload Protection | AC Mode:Warning only @ 110%>Load>105%, Transfer to bypass after 60sec @ 120%>Load>110%, Transfer to bypass immediately@ Load>120%
Battery Mode:Warning only @ 110%>Load>105%, Shutdown after 10sec @ 120%>Load>110%, Shutdown immediately @ Load>120%
Bypass Mode:Warning only @ 130%>Load>105%, Shutdown immediately @ Load>130% |
| Surge Protection and Filtering |
| Surge Protection | Yes |
| DSL/Phone/Fax/Modem protection | RJ11/RJ45(One In/One Out) |
| Short Circuit Protection | UPS Output Cut off Immediately or Circuit Breaker Protection |
| Physical |
| Receptacles | (4) IEC C13 + Terminal Block |
| Dimensions(H x W x D)(mm) | 337 x 196 x 416 |
| Weight(kg) | 12.2 |
| Battery |
| Sealed Maintenance Free Lead Acid Battery | Depends on external batteries |
| Typical Recharge Time | Depends on external batteries. Built-in Charger (8A max.) |
| Runtimes |
| Half load-Full load (mins) | Depends on external batteries |
| Status Indication |
| Indicators | Power On, Line Mode, Battery Mode, Bypass Mode, ECO Mode, C/F Mode, Fault, Replace Battery |
| Audible Alarms | Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery |
| Communication |
| Power Management Software | PowerPanel® Business Edition |
| Management |
| Self-Test | Yes |
| Auto-Charge/Auto-Restart | Yes |
| Auto-Overload Recovery | Yes |
| Cold Start(DC Start) | Yes |
| Connectivity Ports | (1) Serial Port (RS232), (1) USB Port, (1) EPO/ROO |
| SNMP/HTTP Capable | Optional |