Model | OLS3000EXL |
Capacity(VA/W) | 3000VA / 2400W |
Typology | Online (Double Conversion) |
Input |
Voltage Range | 120~139Vac for 0~25% Load
140~159Vac for 0~50% Load
160~179Vac for 0~75% Load
180~280Vac for 0~100% Load |
Frequency Range | 40~70Hz |
Output |
Voltage Range | Pure Sinewave at 200, 208, 220, 230, 240Vac (Configurable) ±1% |
Frequency Range | 50 / 60Hz (Auto-Sensing or Configurable) ±0.5Hz |
Transfer Time (Typical) | 0ms |
Overload Protection | AC Mode:Warning only @ 110%>Load>105%, Transfer to bypass after 60sec @ 120%>Load>110%, Transfer to bypass immediately@ Load>120%
Battery Mode:Warning only @ 110%>Load>105%, Shutdown after 10sec @ 120%>Load>110%, Shutdown immediately @ Load>120%
Bypass Mode:Warning only @ 130%>Load>105%, Shutdown immediately @ Load>130% |
Surge Protection and Filtering |
Surge Protection | Yes |
DSL/Phone/Fax/Modem protection | RJ11/RJ45(One In/One Out) |
Short Circuit Protection | UPS Output Cut off Immediately or Circuit Breaker Protection |
Physical |
Receptacles | (4) IEC C13, (1) IEC C19, Terminal Block |
Dimensions(H x W x D)(mm) | 337 x 196 x 416 |
Weight(kg) | 12.6 |
Battery |
Sealed Maintenance Free Lead Acid Battery | Depends on external batteries |
Typical Recharge Time | Depends on external batteries. Built-in Charger (8A max.) |
Runtimes |
Half load-Full load (mins) | Depends on external batteries |
Status Indication |
Indicators | Power On, Line Mode, Battery Mode, Bypass Mode, ECO Mode, C/F Mode, Fault, Replace Battery |
Audible Alarms | Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery |
Communication |
Power Management Software | PowerPanel® Business Edition |
Management |
Self-Test | Yes |
Auto-Charge/Auto-Restart | Yes |
Auto-Overload Recovery | Yes |
Cold Start(DC Start) | Yes |
Connectivity Ports | (1) Serial Port (RS232), (1) USB Port, (1) EPO/ROO |
SNMP/HTTP Capable | Optional |